Public Works
P.O. Box 150027
Cape Coral, FL 33915-0027
Phone: 239.242.3200
Fax: 239.574.0732
 |
|
|
|
| |
| Reverse Osmosis |
 |
HISTORY:
The City of Cape Coral utilizes reverse osmosis
(RO) to treat its’ water which is supplied by 23 deep wells. The
majority of these wells are in the lower Hawthorne Aquifer at a depth
of 650
to 700 feet. The RO Plant was built in 1976. Prior to the building
of the RO Plant the City used lime softening. This technology was
abandoned in 1985, primarily due to salt water intrusion. The 3 mgd
Reverse Osmosis Plant of 1976 was expanded to 15 mgd, which allows
the City to keep pace with the growth occurring in Cape Coral. |
| |
OPERATIONAL
DATA:
The RO Plant is divided into two sections. The
original Plant, which is referred to here as Plant 1 and the addition,
which was built in 1985, referred to here as Plant 2: |
| |
| |
|
PLANT
1 |
PLANT2 |
| MICRON FILTERS. |
|
|
|
| 1. filters |
|
5 |
10 |
| 2.Cartridges |
|
80 |
52 |
| 3 Length (inches). |
|
40 |
30 |
| 4. Size (microns) |
|
5 |
5 |
| HIGH PRESSURE PUMPS |
|
|
|
| 1. pumps |
|
10 |
8 |
| 2. horsepower |
|
150 |
150 |
| 3. capacity |
|
520GPM |
715GPM |
| REVERSE OSMOSIS UNITS |
|
|
|
| 1.Trains |
|
10 |
8 |
| 2.Vessels/train |
|
24 |
26 |
| 3. Elements/vessel |
|
4 |
7 |
| 4.Elements(Plant) |
|
840 |
1,344 |
| 5.Pressure 1st
stage |
|
250psi |
170psi |
| 6. Recovery rate % |
|
75 |
85 |
| 7. RO capacity |
|
5mgd |
7mgd |
| 8.Current blend rate |
|
1mgd |
2mgd |
| 9. Plant capacity |
|
6mgd |
9mgd |
| 10. Raw Water req. |
|
7.7mgd |
10.2mgd |
| 11. Brine Reject |
|
1.7mgd |
1.2mgd |
| DE-GASIFIERS |
|
|
|
| 1.Number |
|
2 |
2 |
| CLEARWELLS |
|
|
|
| 1. Number |
|
1 |
1 |
| 2. Volume |
|
41,000 gal. |
117,500 gal. |
| STORAGE TANKS |
|
(3) FIVE MG CEMENT
ABOVE GROUND |
|
| |
| For information
on the chemistry of the City's water, click
here to view the Consumer Confidence Report. |
| |
| |
(MCL)
MAXIMUM CONTAMINANT LEVEL ALLOWED |
| |
|